StationaryFULGURIS

5OPzV-350

Model 5OPzV-350

2 V VRLA GEL with tubular positive plate. Float service life of over 15 years at 25 °C.

Datasheet

Specifications

Technology
VRLA GEL with tubular positive plate
Voltage
2 V
Capacity
350 Ah (10 h at 25 °C)
Dimensions
124 × 206 × 489 mm (L × W × H)
Applications
Telecommunications, Industry, Wind energy, Emergency lighting, Signaling, UPS systems, PBX and telephone exchanges, Solar energy, Power generation and transmission, Electrical substations
Service life
Float service life of over 15 years at 25 °C
Jar
5OPzV-STD
Capacity at 20 h
372 Ah
Capacity at 10 h
350 Ah
Capacity at 8 h
336 Ah
Capacity at 5 h
300 Ah
Capacity at 3 h
261 Ah
Capacity at 1 h
185 Ah
Quick overview

Features

  • Tubular positive plates and pasted negative plates, formed through a jar-formation process.
  • Microporous separators and gel-immobilized electrolyte.
  • Flame-retardant ABS jars and covers in DIN OPzV standard.
  • Charge voltage of 2.25 V per cell ±1% at 25 °C.
  • 99% gas recombination efficiency.